Phoenix Lite

Phoenix Lite

Single Phase, Indoor,
Standby Emergency Lighting Inverter
575 to 1050 Watt

The Phoenix Lite series is a single phase, standby, solid state inverter system utilizing DSP/PWM technology. The unit packs all the necessary options and is quickly and simply installed. The Phoenix Lite is designed to function in conjunction with the existing building electrical system to provide high quality surge suppression, power conditioning, backup power protection and distribution for lighting loads and other critical loads.
Email This Page
Your Name Recipient name
Your Email Recipient Email
Message
The information entered on this page will not be used to send unsolicited e-mail and will not be sold to a third party.
FEATURES
  • Standard Power Level: 525, 700, 875, 1050W
  • Input Voltage: 120, 208, 240, 277, 480VAC
  • Input Voltage Range: +10% to 15%
  • Output Voltage: 120, 277, 120/240 or 120/277VAC
  • Output Voltage Regulation: ±5% for all loads and battery discharge mode
  • Output Frequency Range: 60 Hz, ±1%
  • Output Wave Form: Sine-wave <5% @ 100% linear load
  • Crest Factor: 2.5:1 typical
  • Input Protection: Input Main Circuit Breaker
  • Output Protection: Output Main Circuit Breaker
  • Surge Protection: The unit will protect itself and the load against surges defined in ANSI/EEE C62.45 category A/B
  • Battery: Sealed maintenance-free (AGM) lead calcium
  • Recharge Current: Conforms to UL 924 standards
  • External Battery: Provision for hardware connection of external battery cabinets or DC source
  • Efficiency: ≥99% at 100% linear load
  • Audible Noise: <45dBA
  • Operating Temperature: 0º to 40ºC (32º to 104ºF)
  • Storage Temperature: -20º to 60ºC (-4º to 140ºF)
  • Humidity: 5 - 95%, Non-condensing
  • Monitoring: LED Displays Alarms and Diagnostics